这个问题与 在 RHEL7 上监控 Lenovo 系统 x3650 m5 (8871) 上的 CPU 风扇速度。监控风扇后,我需要监控电源的状态。这里ipmitool
不起作用,(它显示假阳性结果)。服务器有 2 个电源。我需要知道其中一个或两个何时关闭/不活动。如何使用命令行工具监控电源?
我确实使用了该ipmitool sdr type Other
命令。输出是
PS Heavy Load | 0Dh | ok | 19.1 | State Deasserted
Power Supply 1 | E0h | ok | 10.1 | Presence detected
Power Supply 2 | E1h | ok | 10.2 | Presence detected
PS Configuration | E2h | ok | 19.1 |
PS 1 Therm Fault | E5h | ok | 10.1 | Transition to OK
PS 2 Therm Fault | E6h | ok | 10.2 | Transition to OK
PS1 12V OV Fault | E7h | ok | 10.1 | Transition to OK
PS2 12V OV Fault | E8h | ok | 10.2 | Transition to OK
PS1 12V UV Fault | E9h | ok | 10.1 | Transition to OK
PS2 12V UV Fault | EAh | ok | 10.2 | Transition to OK
PS1 12V OC Fault | EBh | ok | 10.1 | Transition to OK
PS2 12V OC Fault | ECh | ok | 10.2 | Transition to OK
PS1 12Vaux Fault | EDh | ok | 10.1 | Transition to OK
PS2 12Vaux Fault | EEh | ok | 10.2 | Transition to OK
Power Unit | EFh | ok | 19.1 | Fully Redundant
然而问题是,它告诉我一切正常。当我从 PSU 上拔下电缆时,它仍然告诉我两个 PSU 都在工作。
答案1
尝试:
ipmitool sdr elist
它将显示准确的结果。